Technical data table for the ACS TP

Поиск

General

The technical data sheets (TDS) presented below shall be completely filled in by the Tenderer and presented together with the Tender to the Employer.

Characteristics and guaranteed values included in these sheets shall become a part of the Contract and as such be binding. Deviations from the requirements, without the written agreement with the Employer, are not allowed

The Tenderer shall present all necessary catalogues and data for complete description of the offered equipment, mechanisms, accessories, devices and materials to be used for civil-erection works and commissioning.

The Tenderer shall bear responsibility for any errors, discrepancies or omissions in the characteristics offered by the Tenderer in the TDS.

The Tenderers shall realize that incomplete answers to questions asked mean discrepancy with the requirements of the Employer (Contract requirements), and such incomplete answers may result in the Employer's refusal from such Tenders.

The Tenderers in their Tenders shall confirm general compliance of the Tenders to the requirements of the Employer in general (without any deviations) or incompliance.

If there are any deviations/discrepancies, they shall be described and explained for each item of tables in the column "Note" or in separate sheet.

 

Functional requirement

 

 

Table 1.1: Technical requirements to ACS TP hardware and software

Description Data: Notes
    Required by the Employer Guaranteed by the Contractor  
  Manufacturer      
  Network hardware
1. SCADA system server
1.1 Reserved yes    
1.2 Industrial design, 19’’ Rackmounted yes    
1.3 Reserved power supply 230 VAC yes    
1.4 RAID controller yes    
1.5 Dual Port LAN adapter yes    
1.6 Internal monitoring yes    
1.7 Remote control yes    
2. Gateways
2.1 Industrial design, 19’’ Rackmounted yes    
2.2 Reserved power supply 230 VAC yes    
2.3 Support of IEC 60870-5-101 protocol yes    
2.4 Support of IEC 60870-5-104 protocol yes    
2.5 Internal monitoring yes    
2.6 Remote control yes    
3. Server of time synchronization with GPS receivers
3.1 Support of IEEE 1588 yes    
3.2 Support of NTP(SNTP) yes    
3.3 GPS/GLONASS yes    
4. Network switchers and routers LAN
4.1 Reserved power supply 230 VAC / DC yes    
4.2 Reserving of network connections yes    
4.3 Compliance with IEC 61850-3 yes    
4.4 Compliance with IEEE 1613 yes    
4.5 Compliance with IEC 61000 yes    
4.6 Internal monitoring, watchdog-relay yes    
4.7 SNMP support yes    
4.8 Remote control/ configuration (web. telnet) yes    
5. Reserved power supply 230 VAC / DC
5.1 Inverters 230 V AC/220 V DC – 230 V AC yes    
5.2 Two independent power supply lines yes    
5.3 SNMP support yes    
6. Visualization tools
6.1 WS
6.1.1 Industrial design yes    
6.1.2 Reserved LAN adapter yes    
6.2 Display, diagonal not less 24’’, 2items      
6.2.1 Matrix IPS, viewing angles are not worse than 178’ yes    
6.3 Keyboard and optical mouse yes    
6.4 Remote viewing display
6.4.1 Display, diagonal not less 55’’, 1item yes    
6.4.2 Management (individual or by an operator station) yes    
6.5 Printer black & white
6.5.1 A4 format yes    
6.5.2 Connection via Ethernet yes    
7. Technological function
7.1 Management      
7.1.1 SU 330 kV – circuit-breakers yes    
7.1.2 SU 330 kV - disconnectors yes    
7.1.3 SU 330 kV – earthing blades yes    
7.1.4 SU110 kV – circuit-breakers yes    
7.1.5 SU 110 kV - disconnectors yes    
7.1.6 SU 110 kV – earthing blades yes    
7.1.7 SU 35 kV – circuit-breakers yes    
7.1.8 SU 10 kV – circuit-breakers yes    
7.1.9 SU 35 kV - disconnectors     Perspective
7.1.10 SU 10 kV -trolleys     Perspective
7.1.11 SU 35kV – earthing blades     Perspective
7.1.12 SU 10 kV – earthing blades     Perspective
7.1.13 Automatic Circuit-breaker 0.4 kV of auxiliary system (if operating mechanism is present) yes    
7.1.14 Automatic Circuit-breaker 0.4 kV of DC board (if operation mechanism is present) yes    
7.1.15 OLTC of autotransformers (AT) yes   Perspective
7.1.16 Fire-extinguishing system’s elements (valves, gates) yes    
7.2 Position monitoring      
7.2.1 SU 330 kV – circuit-breakers yes    
7.2.2 SU 330 kV - disconnectors yes    
7.2.3 SU 330 kV – earthing blades yes    
7.2.4 SU110 kV – circuit-breakers yes    
7.2.5 SU 110 kV - disconnectors yes    
7.2.6 SU 110 kV – earthing blades yes    
7.2.7 SU 35 kV – circuit-breakers yes    
7.2.8 SU 10 kV - circuit-breakers yes    
7.2.9 SU 35 kV - disconnectors yes    
7.2.10 SU 10 kV -trolleys yes    
7.2.11 SU 35 kV – earthing blades yes    
7.2.12 SU 10 kV – earthing blades yes    
7.2.13 Automatic Circuit-breaker 0.4 kV of auxiliary system (if operating mechanism is present) yes    
7.2.14 Automatic Circuit-breaker 0.4 kV of DC board (if operation mechanism is present) yes    
7.2.15 OLTC of autotransformers (AT) yes   Perspective
7.2.16 Fire-extinguishing system’s elements (valves, gates) yes    
8. Bay controllers
8.1 IEC 61850 support yes    
8.2 PLC IEC 61131-3 yes    
8.3 Local MMI yes    
8.4 Reserved network connections yes    
9. Integration into ACS TP      
9.1 APAS system yes    
9.2 RP & SA system yes    
9.3 Security video surveillance system yes    
9.4 SURS monitoring system yes    
9.5 Meteorological monitoring system yes    
9.6 Electrical measurements system yes    
9.7 Fire-extinguishing system yes    
9.8 Ventilation and air conditioning system yes    
9.9 DC board (if controller is present) yes    
9.10 Auxiliary board (if controller is present) yes    
9.11 SS main equipment diagnostic system yes    
10. System of data retransmission to higher levels of SS
10.1 IEC 60870-5-104 (101) protocol yes    
11. Software for SHS of ACS TP      
11.1 Basic (firm) software yes    
11.2 Application software yes    
12. Local area network (LAN)
12.1 Fast Ethernet yes    
12.2 Gigabit Ethernet yes    
12.3 IEC 61850 yes    
12.4 IEC 60870-5-101 yes    
12.5 IEC 60870-5-103 yes    
12.6 ІЕС 60870-5-104 yes    
12.7 MODBUS yes    
12.8 PROFIBUS yes    
12.9 DNP yes    
12.10 Use of “ring” scheme yes    
12.11 Use of “star” scheme yes    
13. Reservation of SS LAN
13.1 RSTP yes    
13.2 PRP yes    
13.3 HSR yes    
14. User interface lauguage      
14.1 Ukrainian yes    
14.2 Russian yes    
15. Data export      
15.1 Comtrade yes    
15.2 Excel yes    
15.3 Word yes    
16. Operating requirements      
16.1 Equipment self-diagnostics yes    
16.2 Software self-diagnostics yes    
16.3 Communication channels self-diagnostics yes    
16.4 Fault location testing yes    
17. Requirements to protection of data against unauthorized access      
17.1 Physical protection level yes    
17.2 Software protection level yes    
17.3 Devices polling interval not less than 1 sec yes    
17.4 DB used yes    
17.5 MS SQL Server yes    
17.6 ORACLE Database Server yes    

 

SECTION V. SPECIAL SPECIFICATIONS FOR AUTOMATED metering system

Setting and purpose of creation the system

Purpose ACSEE SS

Automated system of power substations should be established as an automated data-processing system, the main purpose of which - the measurement, collection, processing, storage, display, documentation electric energy accounting data.

 

ACSEE SS should provide:

 

· automated data collection of measurements of parameters of electricity from meters and other data needed for accounting of electric power;

· providing hourly electricity metering;

· obtaining an average of the power at each point of the account and the construction of the half-hour (hourly) load graphs on daily, monthly and annual intervals;

· monitoring the reliability of the measuring data;

· providing simultaneous measurement processes;

· processing of measurement information;

· automated data processing of measurements of parameters of electricity and other energy accounting data and the formation of accounting results that are taken for financial and other calculations;

· automated data saving electricity metering;

· automation of control of technical condition of the accounting system of electricity;

· work with ACS SS;

· interaction with an automated control system of power quality (ACSPQ);

· preparing accounting documents for electricity metering.

 

 

The purpose of the ACSEE SS

The purpose of the ACSEE is:

 

· implementation of requirements of normative documents, decisions of Advice WMEE in relation to the account of electric energy, including relatively for the sentinel of its account on the scopes of balance belonging of subjects of WMEE;

· reduction of commercial losses by increasing the accuracy of electric energy and information that enables the analysis of electric power losses in the main backbone network;

· automation of the collection, transmission and processing of information from the settlement, and technical points of electric energy at the substation;

· ensuring the operational efficiency of the automatic control counters and data channels;

· validation of the data obtained through the formation of the balance of electric energy substations (hereinafter - SS);

· providing of work of all elements of ACSEE PS in the single estimated time with the maintainance of the set rules of passing to the "summer / winter" time;

· decline of labour intensiveness of works on the account of electric energy;

· introduction of modern technical and programmatic facilities high-reliability, by the protracted terms exploitations which provide the minimum terms of return of the inlaid facilities and defence of the inlaid investments;

· providing of personnel of substation by complete information about making, vacation, trunk-to-trunk and consumption of electric power;

· automation of procedures preparation of current documents.

 

 