Technical Data Security Kit CS-110 kV, BCS- 110 kV bus coupler on the current printsipes the breaker failure protection
№
| Description
| Information
| Note
| Required Customer
| Guaranteed Contractor
| Complete backup protection CS-110 kV,BCS- 110 kV bus coupler on the current printsipes the breaker failure protection
| 1.
| Type
|
|
|
| 2.
| Manufacturer
|
|
|
| 3.
| Standards
| IEC 61850
|
|
| 4.
| Technical description
| 4.1
| Number of setting groups, not less
|
|
|
| 4.2
| Number of signaling LEDs thing., Not less
|
|
|
| 5.
| AC circuit terminals
| 5.1
| Rated measuring current, A
| 1.0 or 5.0
|
|
| 5.2
| The number of current inputs, pcs., Not less
|
|
|
| 5.3
| Thermal current (continuous)
| 4 х In
|
|
| 5.4
| The current one-second resistance
| 100 х In
|
|
| 5.5
| Operating range
| (0,1 – 30) x In
|
|
| 5.6
| Consumption per phase at In, VA
| Not less 0,25
|
|
| 5.7
| Operating check current circuits
| Yes
|
|
| 6.
| Operating frequency alternating current circuits and voltage terminals
| 6.1
| Rated frequency, Hz
| fn= 50
|
|
| 6.2
| Operating frequency range
| 50 ± 5%
|
|
| 7.
| Operational DC
| 7.1
| Rated operational voltage DC,V
| Un = 220
|
|
| 7.2
| The working voltage range of the operational DC
| (0,8 – 1,2) x Upn
|
|
| 7.3
| Ripple in the DC voltage
| Not more than 6% of the mean
|
|
| 7.4
| Operation terminals shall not be violated with the disappearance or reduction of lower U-set limit on the time,sec
| 0,04
|
|
| 7.5
| There should be no false positives or disrupt normal function terminals when removing or power supply U
| Yes
|
|
| 7.6
| Подача напряжения питания обратной полярности не должна вызвать повреждение терминала
| Yes
|
|
| 8.
| Binary input terminal
| 8.1
| Rated voltage of each input,V
| Uin.n = 220
|
|
| 8.2
| The operating range of each entry,V
| (0,8 – 1,1)xUin.n
|
|
| 8.3
| Voltage "unwarranted" triggering each input,V
| (0.65 – 0.8)xUin.n
|
|
| 8.4
| The digital inputs must provide:
| 8.4.1
| failure to function when a ground fault on any of the poles;
| Yes
|
|
| 8.4.2
| Malfunction during operation auto search "ground" at fault detection pole
| Yes
|
|
| 8.5
| The dropout ratio
| К ≥ 0,95
|
|
| 8.6
| Freely programmable binary inputs
| Yes
|
|
| 9.
| Contact outputs terminals
| 9.1
| DC Voltage, V
|
|
|
| 9.2
| Exclude galvanic connection with the elements located inside the terminal
| Yes
|
|
| 9.3
| Breaking capacity current 1 / 0,4 / 0,2 A at a voltage of 48/110/220 V and the time constant of the circuit L / R ≤ 40 msec
| Yes
|
|
| 9.4
| Making capacity at inductive load with L / R > 10 msec
| 10 A for a time, sec
| 1,0
|
|
| 30 A for a time, sec
| 0,2
|
|
| 9.5
| A continuous flow of current, A
|
|
|
| 9.6
| Freely programmable output relay
| Yes
|
|
| 10.
| Four zero-sequence overcurrent protection with a choice of direction
| 10.1
| The minimum polarizing voltage
| (0,05 – 0,8) r.u.
|
|
| 10.2
| Tripping current
| (0,08 – 30) r.u.
|
|
| 10.3
| Lock on the second harmonic
| (10 – 100)%
|
|
| 10.4
| Relay characteristic angle
| -95° tо +95°
|
|
| 10.5
| Selecting focus
| Yes
|
|
| 10.6
| Timers,sec
| 0,00 – 60,00
|
|
| 11.
| Instantaneous overcurrent protection from phase faults (50)
| 11.1
| Tripping current
| (0,08 – 4) r.u.
|
|
| 11.2
| The dropout ratio
| > 95%
|
|
| 12.
| Instantaneous overcurrent ground fault (50N)
| 12.1
| Tripping current
| (0,08 – 4) r.u.
|
|
| 12.2
| The dropout ratio
| > 95%
|
|
| 13.
| Function breaker failure protection
| 13.1
| Controlling breaker failure overcurrent, contacts or non-diversion of current and non-diversion of contacts
| Yes
|
|
| 13.2
| Receive triggers protection switching and catch on the lifetime of the current in the breaker failure protection
| yes
|
|
| 13.3
| Phase current operation
| (0,02 – 3) r.u.
|
|
| 13.4
| The current operation of the residual
| (0,001 – 0,8) r.u.
|
|
| 13.5
| Repeat the action on the circuit breaker without delay (action "on itself")
| Yes
|
|
| 13.6
| Return breaker failure timers if successful disconnecting switch
| Yes
|
|
| 13.7
| The dropout ratio of the current body of the breaker failure protection, not less
| 0,9
|
|
| 13.8
| Determining whether the current time, no more than
| 10 msec
|
|
| 13.9
| Timers,sec
| 0,00 – 10,00
|
|
| 14.
| Tripping logic (one drive for three-phase)
| 14.1
| Action trip
| 3-phase
|
|
| 14.2
| Logic of teleacceleration
| Yes
|
|
| 14.3
| Pulse width off (timers),sec
| 0,00 – 50,00
|
|
| 15.
| Measurement
| 15.1
| Frequency
| Yes
|
|
| 15.2
| Current
| Yes
|
|
| 16.
| Event recorder
| 16.1
| The counter value
|
|
|
| 16.2
| The maximum count rate, pulse / s
|
|
|
| 17.
| Disturbance recorder
| 17.1
| The number of recordable analog channels
|
|
|
| 17.2
| Time resolution msec
|
|
|
| 17.3
| The number of events in the list, at least
|
|
|
| 18.
| oscillographic testing
| 18.1
| Starts:
| 18.2
| start-up, dropout, or operate any item;
| Yes
|
|
| 18.3
| change the state of the entrance;
| Yes
|
|
| 18.4
| contact output state change;
| Yes
|
|
| 18.5
| Storage of data in nonvolatile memory
| Yes
|
|
|
|
|
|
|
|
Technical data sets automatic control switch with 110 kV circuit breaker failure protection, AR, FLD
№
| Description
| Information
| Note
| Required Customer
| Guaranteed Contractor
| 1.
| Type
|
|
|
| 2.
| Manufacturer
|
|
|
| 3.
| Standards
| IEC 61850
|
|
| 4.
| Technical description
| 4.1
| Number of setting groups, not less
|
|
|
| 4.2
| Number of signaling LED units.
| ≥12
|
|
| 5.
| AC circuit terminals
| 5.1
| Rated current, A
| In = 1 or 5
|
|
| 5.2
| The number of current inputs, thing, Not less
|
|
|
| 5.3
| Thermal current (continuous)
| 2 x In
|
|
| 5.4
| The current one-second resistance
| 100 x In
|
|
| 5.5
| Operating range
| (0,1 – 30) x In
|
|
| 5.6
| Consumption per phase at In, VA
| Not less 0,5
|
|
| 5.7
| Operating check current circuits
| Yes
|
|
| 6.
| Circuit AC terminals
| 6.1
| Rated secondary voltage,
| Un = 100
|
|
| 6.2
| Number of inputs AC circuits, however, pcs.:
|
|
|
| 6.3
| AC voltage thermal stability (long)
| 1,5 x Un
|
|
| 6.4
| One-second AC voltage stability
| 2,5 x Un
|
|
| 6.5
| Load phase Un, VA
| < 0,5
|
|
| 6.6
| Operating check voltage circuits
| Yes
|
|
| 7.
| Operating frequency alternating current circuits and voltage terminals
| 7.1
| Rated frequency, Hz
| fn = 50
|
|
| 7.2
| Operating frequency range
| (0,95 - 1,05) x fn
|
|
| 8.
| Operational DC
| 8.1
| Rated operational voltage DC,V
| Un = 220
|
|
| 8.2
| The working voltage range of the operational DC
| (0,8 - 1,1) x Upn
|
|
| 8.3
| Ripple in the DC voltage
| Not more than 6% of the mean
|
|
| 8.4
| Normal functioning of the terminals must not be violated in the disappearance or reduction of voltage drops below set limit on the time,sec
| tо 0,04
|
|
| 8.5
| Supply voltage of reverse polarity must not cause damage to the terminal
| Yes
|
|
| 9.
| Binary input terminal
| 9.1
| Rated voltage of each input,V
| Uin.n = 220
|
|
| 9.2
| The operating range of each input
| (0,8 – 1,1) x Uin.n
|
|
| 9.3
| Voltage "unwarranted response" of each entry,V
| (0.65 – 0.8) x Uin.n
|
|
| 9.4
| The digital inputs must provide:
| 9.4.1
| failure to function when a ground fault on any of the poles;
| Yes
|
|
| 9.4.2
| Malfunction during operation auto search "ground" at fault detection at the poles
| Yes
|
|
| 9.5
| The dropout ratio
| К ≥ 0,95
|
|
| 9.6
| Freely programmable binary inputs
| Yes
|
|
| 10.
| Contact outputs terminals
| 10.1
| Commute DC voltage, V
|
|
|
| 10.2
| Exclude galvanic connection with the elements located inside the terminal
| Yes
|
|
| 10.3
| Making capacity at inductive load with L / R>10 msec
| 10 A for a time, sec
| 1.0
|
|
| 30 A for a time, sec
| 0.2
|
|
| 10.4
| A continuous flow of current, A
|
|
|
| 10.5
| Breaking capacity current 1 / 0,4 / 0,2 A at a voltage of 48/110/220 V and the time constant of the circuit L / R ≤ 40 msec
| Yes
|
|
| 10.6
| Freely programmable output relay
| Yes
|
|
| 11.
| Function breaker failure protection
| 11.1
| Circuit breaker failure protection with current supervision
| Yes
|
|
| 11.2
| Receiving three-phase operation triggers internal / external protection and catch on the lifetime of the current in the circuit breaker failure protection
| Yes
|
|
| 11.3
| The range of current control operation phase of the measuring body, A
| (0,02 – 3)
|
|
| 11.4
| Repeat the action on the circuit breaker without delay (action "on itself")
| Yes
|
|
| 11.5
| Return breaker failure timers if successful disconnecting switch
| Yes
|
|
| 11.6
| The dropout ratio of the current body of the breaker failure protection to any setting, not less
| 0,9
|
|
| 11.7
| Duration tripping, no more
| 18 msec
|
|
| 11.8
| Determining whether the current time, no more than
| 10 msec
|
|
| 12.
| Automatic reclosing (AR) for the circuit with one breaker
| 12.1
| Number of reclosing attempts
| 1 – 4
|
|
| 12.2
| Program restart
| 3ph;
|
|
| 12.3
| Options TARI, FARI with a choice of the form AR, depending on the type of trip
| Yes
|
|
| 12.4
| Possibility of the prolonged dead time reclosing in case of loss wp link line protection to enable signal
| Yes
|
|
| 12.5
| Control of the circuit breaker to reclose cycle "off-on-off"
| Yes
|
|
| 13.
| Circuit breaker condition monitoring
| 13.1
| Determination disabled state line
| Yes
|
|
| 13.2
| Control Enable or disable switch position
| Yes
|
|
| 14.
| Control functions accession
| 14.1
| Circuit breaker
| Yes
|
|
| 14.2
| Control isolating switch
| Yes
|
|
| 14.3
| Control grounded knives
| Yes
|
|
| 15.
| The control current circuit
| 15.1
| Tripping current
| (0,08 – 4) r.u.
|
|
| 16.
| Fault monitoring circuit AC
| 16.1
| The current operation, reverse the sequence
| (0,05 – 0,5) r.u.
|
|
| 16.2
| The level of change in the current operation
| (0,08 – 30) r.u.
|
|
| 17.
| Tripping logic (one drive for three-phase)
| 17.1
| Action trip
| 3-phase
|
|
| 17.2
| Pulse width off (timers),sec
| 0,00 – 50,00
|
|
| 18.
| Measurement
| 18.1
| Frequency
| Yes
|
|
| 18.2
| Voltage
| Yes
|
|
| 18.3
| Current
| Yes
|
|
| 18.4
| Phase angle
| Yes
|
|
| 18.5
| Аctive power, P
| Yes
|
|
| 18.6
| Reactive power, Q
| Yes
|
|
| 18.7
| Full power, S
| Yes
|
|
| 18.8
| Power factor, cos (ϕ)
| Yes
|
|
| 19.
| Event Counter
| 19.1
| The counter value
|
|
|
| 19.2
| The maximum count rate, pulse / s
|
|
|
| 20.
| Disturbance recorder
| 20.1
| The number of recordable analog channels
|
|
|
| 20.2
| Time resolution,msec
|
|
|
| 20.3
| The number of events in the list, at least
|
|
|
| 21.
| Fixing the position of the switch
| 21.1
| Fixing off line to FARI
| Yes
|
|
| 21.2
| Locking off the line after NFARI
| Yes
|
|
| 21.3
| Fixing the inclusion of the WL
| Yes
|
|
|
|
|
|
|
| | | | | | | | |
|