Set differential busbar protection T-110/35 kV
| |
1.
| Type
|
|
|
|
2.
| Manufacturer
|
|
|
|
3.
| Standards
| IEC 61850
|
|
|
4.
| Technical description
|
4.1
| Number of setting groups, not less
|
|
|
|
4.2
| Number of signaling LEDs pcs., Not less
|
|
|
|
5.
| AC circuit terminals
|
5.1
| Rated measuring current, A
| 1.0 or 5.0
|
|
|
5.2
| The number of current inputs, things, Not less
|
|
|
|
5.3
| Thermal current (continuous)
| 4 х In
|
|
|
5.4
| The current one-second resistance
| 100 х In
|
|
|
5.5
| Operating range
| (0,1 – 100) x In
|
|
|
5.6
| Consumption per phase at In, VA
| Not less 0,3
|
|
|
5.7
| Operating check current circuits
| Yes
|
|
|
6.
| Circuit AC terminals
|
6.1
| Nominal test voltage,
| Un = 100
|
|
|
6.2
| Number of voltage inputs, however, units.
|
|
|
|
6.3
| Overload (long)
| 420 V
|
|
|
6.4
| Permissible ten-overload
| 450 V
|
|
|
6.5
| Power consumption per phase, VA
| < 0.3
|
|
|
6.6
| Operating check voltage circuits
| Yes
|
|
|
7.
| Operating frequency alternating current circuits and voltage terminals
|
7.1
| Operating frequency alternating current circuits and voltage terminals
| fn= 50
|
|
|
7.2
| Operating frequency range
| 50 ± 5%
|
|
|
8.
| Operational DC
|
8.1
| Rated operational voltage DC,V
| Un = 220
|
|
|
8.2
| The allowable voltage range
| (0,8 – 1,1) x Upn
|
|
|
8.3
| Ripple in the DC voltage
| Not more than 6% of the mean
|
|
|
8.4
| Operation terminals shall not be violated with the disappearance or reduction of lower U-set limit on the time,sec
| 0,04
|
|
|
8.5
| There should be no false positives or disrupt normal function terminals when removing or power supply U
| yes
|
|
|
8.6
| Supply voltage of reverse polarity must not cause damage to the terminal
| Yes
|
|
|
9.
| Binary input terminal
|
9.1
| Rated voltage of each input,V
| Uin.n = 220
|
|
|
9.2
| The operating range for each input
| (0,8 – 1,1) x Uin.n
|
|
|
9.3
| Voltage 'unwarranted" triggering each input V
| (0.65 – 0.8) x Uin.n
|
|
|
9.4
| The digital inputs must provide:
|
9.4.1
| failure to function when a ground fault on any of the poles;
| Yes
|
|
|
9.4.2
| Malfunction during operation auto search "ground" at fault detection pole
| Yes
|
|
|
9.5
| The dropout ratio
| К ≥ 0,95
|
|
|
9.6
| Freely programmable digital inputs
| Yes
|
|
|
10.
| Contact outputs terminals
|
10.1
| Commute DC voltage, V
|
|
|
|
10.2
| Exclude galvanic connection with the elements located inside the terminal
| Yes
|
|
|
10.3
| Making capacity at inductive load with L / R >10 msec
| 10 A for a time, sec
| 1.0
|
|
|
30 A for a time, sec
| 0.2
|
|
|
10.4
| A continuous flow of current, A
|
|
|
|
10.5
| Breaking capacity current 1 / 0,4 / 0,2 A at a voltage of 48/110/220 V and the time constant of the circuit L / R ≤ 40 msec
| yes
|
|
|
10.6
| Freely programmable output relay
| Yes
|
|
|
11.
| Дифференциальная защита
|
11.1
| Minimum relative operating current
| (0.1 – 0.6) r.u.
|
|
|
11.2
| Brake current end of Phase 1
| (0.2 – 1.5) r.u.
|
|
|
11.3
| Differential current end of Phase 2
| (1.0 – 10) r.u.
|
|
|
11.4
| The slope portion 2 braking characteristics
| (10.0 – 50.0) %
|
|
|
11.5
| Slope portion 3 brake characteristics
| (30.0 – 100.0) %
|
|
|
11.6
| Differential section
| (2.5 – 30) r.u.
|
|
|
11.7
| Lock on the second harmonic
| (5.0 – 50.0) %
|
|
|
11.8
| Blocking the fifth harmonic
| (5.0 – 100.0) %
|
|
|
12.
| Differential protection zero sequence
|
12.1
| Minimum relative operating current
| (0,02 – 1) r.u.
|
|
|
12.2
| Brake current end of the 1st section
| (0.1 – 10.0) r.u.
|
|
|
12.3
| The slope of the phase 2
| (0 – 150) %
|
|
|
12.4
| The slope of the phase 3
| (15 – 150) %
|
|
|
13.
| Thermal overload protection
|
13.1
| The level of alarm
| (50 – 99) % enthalpy
|
|
|
13.2
| Tripping current
| (0,1 – 4) r.u.
|
|
|
13.3
| Return of excess temperature level
| (10-95)% off enthalpy
|
|
|
14.
| Current protection zero sequence
|
14.1
| 3U0>Dir
| (0.5 – 80) %
|
|
|
14.2
| Minimum current operation
| (0.08 – 4) r.u.
|
|
|
14.3
| Relay characteristic angle
| – 95° tо +95°
|
|
|
15.
| overcurrent protection
|
15.1
| Minimum current operation
| (0.002 - 60.0) r.u.
|
|
|
15.2
| Relay characteristic angle
| – 95° tо +95°
|
|
|
16.
| Distance protection (21)
|
16.1
| Number of zones
|
|
|
|
16.2
| Characteristic
| quadrangular
|
|
|
16.3
| Setting resistance, Ohm
| 0,05 tо 500,00
|
|
|
16.4
| Error setting resistance
| ± 5 %
|
|
|
16.5
| Remote characteristic angle
| 30 to 90 ° in step of 1
|
|
|
| Control orientation:
|
16.6
| Characteristic angle
| 30 to 90 ° in step of 1
|
|
|
16.7
| The maximum angle
| 30 to 90 ° in step of 1
|
|
|
16.8
| Exposure time,sec
| 0,00 tо 10,00
|
|
|
17.
| Ground distance protection (21N)
|
17.1
| Number of zones
|
|
|
|
17.2
| Characteristic
| quadrangular
|
|
|
17.3
| Setting resistance, Ohm
| 0,05 tо 500,00
|
|
|
17.4
| Remote characteristic angle
| 30 to 90 ° in step of 1
|
|
|
| Control orientation:
|
17.5
| Characteristic angle
| 30 to 90 ° in step of 1
|
|
|
17.6
| The maximum angle
| 30 to 90 ° in step of 1
|
|
|
| Compensation for residual:
|
|
|
|
17.7
| Amplitude Z0/Z1
| 0,00 tо 10,00
|
|
|
17.8
| Angle Z0/Z1
| –90 tо 90°
|
|
|
| Compensation of mutual zero sequence:
|
17.9
| Amplitude Z0М/Z1
| 0,00 tо 7,00
|
|
|
17.10
| Angle Z0М/Z1
| –90 tо 90°
|
|
|
17.11
| Exposure time,sec
| 0,00 tо 10,00
|
|
|
18.
| The control current circuit
|
18.1
| Tripping current
| (5 – 100) %
|
|
|
19.
| Operating check circuit AC
|
19.1
| The current operation, reverse the sequence
| (0,05 – 0,5) r.u.
|
|
|
19.2
| The level of change in the current operation
| (0,08 – 30) r.u.
|
|
|
20.
| Tripping logic
|
20.1
| Action trip
| 3-phase
|
|
|
20.2
| Pulse width off (timers),sec
| 0,00 – 50,00
|
|
|
21.
| Measurement
|
21.1
| Frequency
| Yes
|
|
|
21.2
| Voltage
| Yes
|
|
|
21.3
| Current
| Yes
|
|
|
21.4
| Phase angle
| Yes
|
|
|
21.5
| Active power, P
| Yes
|
|
|
21.6
| Reactive power, Q
| Yes
|
|
|
21.7
| Full power, S
| Yes
|
|
|
21.8
| Power factor, cos (ϕ)
| Yes
|
|
|
22.
| Event recorder
|
22.1
| Capacity,events
|
|
|
|
22.2
| The maximum count rate, pulse / s
|
|
|
|
23.
| Disturbance recorder
|
23.1
| The number of recordable analog channels
|
|
|
|
23.2
| The number of recordable analog channels
|
|
|
|
23.3
| The number of events in the list, at least
|
|
|
|
24.
| oscillographic testing
|
24.1
| Starts:
|
|
|
|
24.2
| start-up, dropout, or operate any item;
| Yes
|
|
|
24.3
| change the state of the entrance;
| Yes
|
|
|
24.4
| contact output state change;
| Yes
|
|
|
24.5
| Storage of data in nonvolatile memory
| Yes
|
|
|
|
|
|
|
|
| | | | | | |
№
| Description
| Information:
| Note
|
Required Customer
| Guranteed Contractor
|
1.
| Type
|
|
| Analog AM RP "Diamant" NPP "Hartron-INKOR"
|
2.
| Manufacturer
|
|
|
3.
| Standards
|
|
|
|
4.
| Technical description
|
4.1
| Rated measuring current, A
| 1.0 or 5.0
|
|
|
4.2
| Nominal test voltage,V
|
|
|
|
4.3
| Rated voltage (DC), V
| =220
|
|
|
4.4
| Voltage reliable switching digital input,V
| 145-242
|
|
|
4.5
| Power failure safe digital input,V
| 0-132
|
|
|
4.6
| The number of current inputs (1A), at least, things
|
|
|
|
4.7
| Number of voltage inputs, however, units.
|
|
|
|
4.8
| The response time of current, msec, max
|
|
|
|
4.9
| Delay time "Repair line" sec
| 0 – 300
|
|
|
4.10
| The delay signal "Fixing enable line after repair";, sec
| 0 – 100
|
|
|
4.11
| Digital inputs
| Yes
|
|
|
4.12
| Digital outputs (relay outputs)
| Yes
|
|
|
5.
| Controlled current settings
|
5.1
| Fixing the lack of current line
| Yes
|
|
|
5.2
| Fixing the lack of power lines
| Yes
|
|
|
5.3
| Disable line tripping relay protection
| Yes
|
|
|
5.4
| Disabling line apparatus side
| Yes
|
|
|
5.5
| Disabling line at the opposite end
| Yes
|
|
|
5.6
| Fixing off line NFARI
| Yes
|
|
|
5.7
| Fixation off line at the opposite end
| Yes
|
|
|
5.8
| Turning to the opposite end of the line
| Yes
|
|
|
5.9
| Switching apparatus side line
| Yes
|
|
|
5.10
| Repair line mode
| Yes
|
|
|
5.11
| Enable line after repair
| Yes
|
|
|
|
|
|
|
|